In this article, we will explore the connection issues that can occur when trying to set up a connection between a Simatic S7-1214 DC/DC/DC CPU and a TP700 comfort panel. We will also provide solutions to overcome these challenges.
The Problem:
When trying to send something from the PLC (CPU) to the HMI (TP700), nothing is happening. However, when simulating the runtime on the PC, the commands from and to the CPU are working fine, indicating that the problem lies with the HMI itself.
Initial Troubleshooting:
To troubleshoot this issue, we tried turning off all security settings for both the HMI and CPU connections and still, the connection was not established. This suggests that there may be a compatibility issue between the firmware versions of the HMI and CPU.
Firmware Downgrade Solution:
After further investigation, it was discovered that downgrading the firmware of the HMI from V17.0.0.0 to V16.0.0.0 resolved the connection issues. This suggests that there is a compatibility issue between the firmware versions of the HMI and CPU.
Additional Tips:
- For more information on security features in TIA Portal V17, please refer to the following links:
- Questions and answers about the security features as of TIA Portal V17
- Why is it not possible to establish a connection to a CPU with firmware version 2.9/4.5 from an HMI panel (Basic, Comfort or Unified) or WinCC Runtime Advanced V17 or lower?
- For image files and other documentation related to SIMATIC HMI Operator Panels: Comfort / Mobile / Basic Panels, please refer to the following link:
- Image Downloads for SIMATIC HMI Operator Panels: Comfort / Mobile / Basic Panels, by downgrading the firmware of the HMI from V17.0.0.0 to V16.0.0.0, we were able to successfully establish a connection between the Simatic S7-1200 CPU and TP700 comfort panel. This solution can be applied when encountering similar compatibility issues with different firmware versions.
References:
- MKesan (2024, May 15). Can you help me? How do I downgrade the firmware v17 to v16?
- Wizard (2024, May 15). Image Downloads for SIMATIC HMI Operator Panels: Comfort / Mobile / Basic Panels
Keywords: Simatic S7-1200 CPU, TP700 comfort panel, TIA Portal V17, firmware downgrade.